ZEROLINE 60

 

Company
Products
Calibration



ZERO
LINE 60 - high precision fault loop impedance and line impedance measurement

ZEROLINE 60

Features:
- Fault loop impedance measurement, resolution 0.001 Ω
- Line impedance measurement, resolution 0.001 Ω
- Fault loop resistance, no trip-out of RCD in RCD protected installation
- Max. value of Z/R - value which takes into consideration operating error of the ZEROLINE 60
- Prospective short-circuit current
- Earth resistance (substitute method)
- AC voltage and frequency
- Automatic check of dangerous voltage on PE
- Automatic check, if test leads are properly connected to tested installation
- Automatic exchange of L/N terminals, if L/N test leads are connected reversely to tested installation
- Automatic protection against overheating of internal power circuits

Technical specification:

Fault loop impedance
Measuring range 0.000 ÷ 1.500 Ω (I test = 30 A)
0.000 ÷ 3.000 Ω (I test = 20 A)
0.000 ÷ 5.000 Ω (I test = 10 A)
Operating range of use
(according to EN 61557-3)
0.038 ÷ 1.500 Ω (I test = 30 A)
0.040 ÷ 3.000 Ω (I test = 20 A)
0.060 ÷ 5.000 Ω (I test = 10 A)
Resolution 0.001 Ω
Reference error ± (2% R + 8 D)* (I test = 30 A)
± (3% R + 8 D)* (I test = 20 A)
± (3% R + 10 D)* (I test = 10 A)
Operating error ± (3% R + 10 D)* (I test = 30 A)
± (4% R + 10 D)* (I test = 20 A)
± (4% R + 15 D)* (I test = 10 A)
Test current (at 230 V / 50 Hz) selectable: 10 A, 20 A, 30 A

Fault loop resistance - quick method
Measuring range 0.00 ÷ 20.00 Ω
Operating range of use
(according to EN 61557-3)
0.20 ÷ 20.00 Ω
Resolution 0.01 Ω
Reference error ± (3% R + 5 D)*
Operating error ± (4% R + 5 D)*
Test current (at 230 V / 50 Hz) 10 A

Fault loop resistance - no trip-out of RCD in RCD protected installation
Measuring range 0.00 ÷ 20.00 Ω
Operating range of use
(according to EN 61557-3)
0.42 ÷ 20.00 Ω
Resolution 0.01 Ω
Reference error ± (5% R + 8 D)*
Operating error ± (6% R + 10 D)*
Test current (at 230 V / 50 Hz) 10 A

Line impedance
Measuring range 0.000 ÷ 5.000 Ω
Operating range of use
(according to EN 61557-3)
0.057 ÷ 5.000 Ω
Resolution 0.001 Ω
Reference error ± (2,5% R + 10 D)*
Operating error ± (3,5% R + 15 D)*
Test current (at 230 V / 400 V, 50 Hz) 10 A / 18 A

Line resistance - quick method
Measuring range 0.00 ÷ 20.00 Ω
Operating range of use
(according to EN 61557-3)
0.20 ÷ 20.00 Ω
Resolution 0.01 Ω
Reference error ± (3% R + 5 D)*
Operating error ± (4% R + 5 D)*
Test current (at 230 V / 400 V, 50 Hz) 10 A / 18 A

Voltage L-PE, L-N, L-L
Measuring range 200 ÷ 440 V
Resolution 1 V
Reference error ± (2% R + 3 D)*
Operating error ± (3% R + 5 D)*

Frequency
Measuring range 48.00 ÷ 52.00 Hz
Resolution 0.01 Hz
Reference error ± (2% R + 10 D)*
Operating error ± (3% R + 10 D)*

General
Line voltage 200 ÷ 440 V / 50 Hz
Protective class II (double insulation)
Over voltage class CAT III / 300 V
Pollution degree 2
Degree of protection IP 40
Dimensions 150 x 190 x 70 mm
Mass about 1.6 kg
* R: Reading, D: Digit

Included in the set: ZEROLINE 60, test cable (6-wires), crocodile clip black, crocodile clip green/yellow, test tip black, test tip blue, neck strip, calibration certificate, instruction manual.

Optional accessories:
P 6120 Bag for the instrument and for some accessories
P 2071 Test cable with 230 V Euro/Schuko plug
P 4011 Crocodile clip, black
P 4013 Crocodile clip, green/yellow
P 3011 Test tip, black
P 3012 Test tip, blue