ALF 10 - 10 A AC earth bond resistance and voltage drop meter

Features:
- Earth bond voltage drop at 10 A AC (EN 60204-1)
- Earth bond resistance at 10 A AC
- Earth bond resistance of appliances (EN 60364)
- Adjustable wire cross-section (EN 60204-1)
- Auto start
- Timer
Technical specification:
Display range -
resistance
- voltage drop |
0.00 ÷ 1.50 Ω 0.0 ÷ 4.5 V |
| Error |
± (1.5% R + 5 D)* |
| Open-circuit voltage |
about 6,5 V AC |
| Short-circuit current |
> 10 A AC |
| Power supply |
230 V ±
10 % / 50 Hz |
| Display |
LCD alphanumeric with backlight |
| Protective class |
II (double insulation) |
| Over voltage class |
CAT II |
| Dimensions |
155 x 135 x 65 mm |
| Weight |
950 g |
| Applied standards: EN 61010-1, EN 60204-1, EMC
standards |
* R: Reading, D: Digit
Included in the set:
ALF 10, test leads 1 m, test lead 2,5 m, test tip 2 pcs, calibration
certificate,
instruction manual.
Optional accessories:
| P 6010 |
Carrying bag |
| P 4011 |
Crocodile clip |
Copyright © 1999-2011 ILLKO, s.r.o.
Subject to changes without notice.
illko@illko.cz
Updated